The functions on this page are written in XML, in a *_fnc chain, and run when the attribute is written: alarms (ALM), conditions that skip part of a chain (IF), filters that hold a change back (FILTER), an on-off controller (CTRL), and the PRO functions every protocol shares — the ones that poll a block, cut it into points and send a write. Why a write runs a chain is 02_Timers_and_Events; the <con>/<dev>/<bi>/<io> tree is 01_The_Element_Tree; the health bits and device alarms are 12_Keeping_It_Running.

How these functions run

A chain runs left to right before the value is stored. A function can let it go on, stop it, or make it skip:

What the function does The rest of the chain The value
goes on runs stored
stops it (PRO.out, PRO.set, a held FILTER, PRO.req …) does not run not stored
a failed IF.* skipped until IF.else / IF.end stored

An alarm function does not write sta itself. It changes the level in the event (evt.stan, which a script later in the chain can read); the engine writes sta when the chain is over, and that write runs the element's sta_fnc — which is where ALM.put, ALM.msk, ALM.lnk and ALM.tim sit.

Before 4.4.2.703 a chain was at most 63 characters

Since 4.4.2.703 a chain may be as long as it needs (an 88-character val_fnc runs whole). Before it, val_fnc, pro_fnc, sta_fnc and xdb_fnc kept 63 characters: a longer list was cut, lost its closing ], and nothing in it ran — no error, no line. With an older engine put a long tail into one script function.

ALM: alarms

An alarm is not an object. It is the level in the element's own sta, and how it is handled:

sta bits Meaning
0x000C level: 0x0004 WARNING, 0x0008 ALARM, 0x000C EMERGENCY, 0 normal
0x00C0 handling: 0x0040 NEW (not acknowledged), 0x0080 SUP, 0x00C0 INH (inhibited)

The value functions (onlvl, onequ, onand, onin) share these rules, measured on ALM.onlvl:

  • Only a running value is judged. With the run state WAITING (0x0302) nothing is raised; when sta goes back to 0x0303 nothing is judged either until the value next changes.
  • Only a change is judged. Writing the same value again does nothing. The value in the file at start is not judged: val="96" with a limit of 90 starts as 0x0303.
  • A rise sets NEW. 0x0303 → 0x034B for an alarm. A return to normal keeps NEW until someone acknowledges: 0x0343.
  • To acknowledge, write sta with NEW cleared: sta &= ~0x0040 gives 0x030B. A later change at the same level leaves it acknowledged; a new level sets NEW again. An acknowledged alarm that clears goes straight to 0x0303.
  • Writing 0x0303 clears the level of a value alarm until the value next changes: 0x034F → 0x0303, then 97 → 0x034F again. (The health bits of <xdb>, <con> and <thr> behave differently: 12_Keeping_It_Running.)
  • INH (sta 0x03C3) holds the level at 0 whatever the value. SUP (0x0080) does not hold: the next alarm writes NEW over it (0x0383 → 0x034B).

Every change of the level writes one WARN line and, when the document has an alm_adr, one record:

ALM.onlhi: id('LVL')/@val ! 'alm_onlhi_alm' -> sta = 0x034B
{"tim":1794389499975,"uid":111263334298192,"src":"S01","knd":"alm","doc":"XDB","rid":"LVL",
 "atr":"val","valp":"85","valn":"90","stap":839,"stan":843,"fnc":"onlhi","valr":"90",
 "pri":0,"desc":"tank level"}

fnc is the function (onlhi above the high limits, onllo below the low ones, onlvl for a return to normal, onequ, onand, onin, onsta, devsta_<why>, or the name given to ALM.send), valr the limit that decided, pri the element's <atr>_alm_pri, desc its desc, stap/stan the sta before and after as numbers. Where the record goes — a history table, the journal, another node — is 11_Records_and_Saving. Without alm_adr the level is set and logged all the same.

A delay. Two attributes on the element (not per attribute) hold a change back:

Attribute Unit Effect
alm_dly_set s a rise is applied this long after the crossing, if the value is still beyond the limit then
alm_dly_rst s a return to normal is applied this long after

Measured with alm_dly_set="2" alm_dly_rst="1": a write of 91 left sta at 0x0303 for 2 s, then 0x034B, and the record's tim was the moment of the crossing. A value back below the limit within the 2 s recorded nothing at all. The engine also keeps alm_tim (ms) on the element: the time of the last change. A write made in xdb_start, before the document runs, is applied at once.

There is no hysteresis or deadband: a value that wanders around a limit raises and clears on every crossing. alm_dly_set / alm_dly_rst are the filter.

ALM.onlvl

In: val_fnc (any <atr>_fnc). Reads: <atr>_alm_onlhi_wrn, _onlhi_alm, _onlhi_emr, <atr>_alm_onllo_wrn, _onllo_alm, _onllo_emr, <atr>_alm_pri, alm_dly_set, alm_dly_rst. Changes: the level in sta.

Six limits, any of them left out. A high limit is reached at or above it, a low limit at or below it; EMERGENCY is tested first, then ALARM, then WARNING. The chain goes on.

<var id="LVL" desc="tank level" val="50" val_typ="0x1308" sta="0x0303" sta_typ="0x1142"
     val_fnc="[ALM.onlvl]"
     val_alm_onlhi_wrn="80" val_alm_onlhi_alm="90" val_alm_onlhi_emr="95"
     val_alm_onllo_wrn="20" val_alm_onllo_alm="10" val_alm_onllo_emr="5"/>
Written sta Record fnc
80 0x0347 onlhi (valr 80)
85 0x0347 — (same level)
90 0x034B onlhi
95 0x034F onlhi
92 0x034B onlhi (valr 90)
50 0x0343 onlvl (cleared, NEW kept)
20 / 10 / 5 0x0347 / 0x034B / 0x034F onllo
NaN 0x034F onlhi: NaN is above every high limit
Infinity / -Infinity 0x034F onlhi / onllo

The limits compare as the value compares: a text value (val_typ="0x1401") is compared as text, so "100" is below "90" and raises nothing. Give a value that is a number a number type. Used in PRJEDU_modbus and PRJEDU_records.

ALM.onequ

In: val_fnc. Reads: <atr>_alm_onequ_wrn, _alm, _emr. Changes: the level.

The level of the first of EMERGENCY, ALARM, WARNING whose value equals the value written. Numbers and text both work.

<var id="MODE" val="0" val_typ="0x1104" sta="0x0303" sta_typ="0x1142" val_fnc="[ALM.onequ]"
     val_alm_onequ_alm="3" val_alm_onequ_wrn="2"/>
<var id="STATE" val="OK" val_typ="0x1401" sta="0x0303" sta_typ="0x1142" val_fnc="[ALM.onequ]"
     val_alm_onequ_emr="FAULT"/>

MODE 2 → 0x0347, 3 → 0x034B, 4 → 0x0343. STATE "FAULT" → 0x034F, "OK" → 0x0343.

ALM.onand

In: val_fnc. Reads: <atr>_alm_onand_wrn, _alm, _emr, _wai — each a bit mask with a number type (_typ). Changes: the level, and the run state.

A level is raised when the value AND its mask is not 0. _wai is different: a match puts the element into WAITING.

<var id="FLAGS" val="0" val_typ="0x1104" sta="0x0303" sta_typ="0x1142" val_fnc="[ALM.onand]"
     val_alm_onand_alm="0x0004" val_alm_onand_alm_typ="0x0144"
     val_alm_onand_wrn="1"      val_alm_onand_wrn_typ="0x0104"/>

1 → 0x0347, 5 → 0x034B. Two traps, both measured: a mask with no _typ is text, and text AND a number is never true — val_alm_onand_alm="0x0004" alone raises nothing, ever. And _wai: 0x80 against _wai="0x0080" gave 0x0342, and from then on nothing, because WAITING is not judged; only a write of sta brings it back.

ALM.onin

In: val_fnc. Reads: <atr>_alm_onin_wrn, _alm, _emr: a list of integers in brackets, "[3,5,7]". Changes: the level.

<var id="LINK" val="1" val_typ="0x1104" sta="0x0303" sta_typ="0x1142" val_fnc="[ALM.onin]"
     val_alm_onin_alm="[0]"/>

The usual use: a 1/0 point that is an alarm at 0 (PRJPER_tello). Measured with _alm="[3,5,7]" _wrn="[1]": 1 → 0x0347, 5 → 0x034B, 4 → 0x0343. Only whole numbers.

ALM.onsta

In: sta_fnc. Reads: sta_alm_onsta_wrn, _alm, _emr — a sta value whose run nibble is compared. Changes: the level.

Raises the level when the run state equals the one named:

<var id="PUMP" val="0" sta="0x0303" sta_typ="0x142" sta_fnc="[ALM.onsta]" sta_alm_onsta_alm="0x0002"/>

sta 0x0302 → 0x034A, 0x0303 → 0x0343. An element that passes through WAITING while the document starts records that alarm and its clear at start.

ALM.onalmlnk

In: val_fnc of a value that carries alarm levels from elsewhere. Reads: the value. Changes: the level, without NEW, record or line.

The value is read in 2-bit parts; the highest part is the level (1 WARNING, 2 ALARM, 3 EMERGENCY). It is the receiving end of ALM.lnk.

<var id="ZONE" val="0" val_typ="0x1144" sta="0x0303" sta_typ="0x1142" val_fnc="[ALM.onalmlnk]"/>

0x0110 → 0x0307, 0x0300 → 0x030F, 0 → 0x0303.

ALM.onstalnk

In: val_fnc. Reads: the value. Changes: the level, without NEW, record or line.

The value is read in 4-bit parts, each a sta run nibble; the highest alarm level among them is taken. 0x3663 → 0x0307, 0x030B → 0x030B, 0 → 0x0303.

ALM.put

In: sta_fnc. Reads: sta_alm_put_cfg, sta_alm_put_<state>, sta_alm_put_lnk_<state>, sta_alm_put_lnk — always these sta_ names. Changes: the addresses named.

When the level (or the run state) changes, writes the value given for the new state to an address: the state's own _lnk_<state>, else the common _lnk.

sta_alm_put_cfg bit State bit State
0x80 emergency (emr) 0x08 running (run)
0x40 alarm (alm) 0x04 waiting (wai)
0x20 warning (wrn) 0x02 stopped (man)
0x10 normal (nrm) 0x01 off (dis)
<var id="TANK" val="50" val_typ="0x1308" sta="0x0303" sta_typ="0x1142" val_fnc="[ALM.onlvl]"
     val_alm_onlhi_alm="90" val_alm_onlhi_wrn="80"
     sta_fnc="[ALM.put]" sta_alm_put_cfg="0x0070" sta_alm_put_alm="2" sta_alm_put_wrn="1" sta_alm_put_nrm="0"
     sta_alm_put_lnk="id('LAMP')/@val" sta_alm_put_lnk_alm="id('HORN')/@val"/>

85 → LAMP.val 1; 91 → HORN.val 2 (its own link); 50 → LAMP.val 0.

ALM.msk

In: sta_fnc. Reads: sta_alm_msk_cfg, sta_alm_msk_lnk, sta_alm_msk_<state>. Changes: some bits of the address.

Packs the state into a few bits of a shared word, so many elements report into one value. sta_alm_msk_cfg = 0x000BIISS: SS the states (the bits of ALM.put), II the position, B the bits per element (2 when 0). The first state that applies, in the order off, stopped, waiting, emergency, alarm, warning, normal, running, writes its sta_alm_msk_<state>, or 1, 1, 1, 3, 2, 1, 0, 0 when that is absent.

<var id="P4" val="50" val_typ="0x1308" sta="0x0303" sta_typ="0x1142" val_fnc="[ALM.onlvl]"
     val_alm_onlhi_alm="90" val_alm_onlhi_wrn="80"
     sta_fnc="[ALM.msk]" sta_alm_msk_cfg="0x000004F0" sta_alm_msk_lnk="id('SUMMARY')/@val"/>

Position 4 × 2 bits: 85 → SUMMARY 0x0100, 91 → 0x0200, 50 → 0x0000. The other bits of SUMMARY are kept.

ALM.lnk

In: sta_fnc. Reads: sta_alm_lnk (address), sta_alm_lnk_idx (position, in 2-bit steps), sta_alm_lnk_map. Changes: 2 bits of the address.

Writes the state as 2 bits at position idx. sta_alm_lnk_map has one hex digit per state, from the right: off, stopped, waiting, running, normal, warning, alarm, emergency; the larger of the run state's digit and the level's digit is written. Without a map it is 0x32101011.

<var id="P5" val="50" val_typ="0x1308" sta="0x0303" sta_typ="0x1142" val_fnc="[ALM.onlvl]"
     val_alm_onlhi_alm="90" val_alm_onlhi_wrn="80"
     sta_fnc="[ALM.lnk]" sta_alm_lnk="id('SUMMARY')/@val" sta_alm_lnk_idx="5"
     sta_alm_lnk_map="0x32100111"/>

With the map above: 85 → SUMMARY 0x0400, 91 → 0x0800, back to 50 → 0x0000. Write your own map. The default gives running the digit 1, so a running point with no alarm writes 1 (a warning): measured with no map, 50 after the alarm gave 0x0400, not 0. 0x32100111 makes running 0 and waiting 1.

ALM.tim

In: sta_fnc, or after an alarm function in val_fnc. Reads: the level change. Changes: <atr>_alm_tim.

On a rise of the level (not on a fall) writes the time in ms since 1970: sta_alm_tim in sta_fnc, val_alm_tim in [ALM.onlvl,ALM.tim]. Measured both: 1794389499998; unchanged when the alarm cleared.

ALM.timstr

As ALM.tim, into <atr>_alm_tim_str, as local time text with its offset: 2026-11-11T02:31:39-0700.

ALM.devsta

In: a <dev>'s sta_fnc — in a plain document PRO.sta runs it for every device by itself. Reads: the device's sta, its blocks' sta, its <con>. Changes: the device's level and run state.

ALARM when no block communicates or the device stopped answering, WARNING when some do and some do not. The record's fnc names why (devsta_nbi, _pbi, _emp, _dwn, _con, _stp, _nrm) and why says it in words; the table and what is not an alarm are in 12_Keeping_It_Running. Measured:

"fnc":"devsta_nbi","why":"none of 1 blocks communicating, waiting: "
"fnc":"devsta_pbi","why":"1 of 3 blocks not communicating: BLKW"

The second one is a trap: BLKW was a block of write points with no timer. A block that is never polled stays WAITING after its device starts, and the device reads WARNING for ever. Put write points under a polled block. Name ALM.devsta yourself only in an edge or hub document (sta_fnc="[IF.edge,PRO.sta,IF.hub,ALM.devsta]"); there PRO.sta does not.

ALM.xdbsta

In: the sta_fnc of an <xdb>, in an edge or hub document; a plain document runs it by itself. Reads: the health bits. Changes: nothing — it only records.

Records every change of the health level of the document as xdbsta_<why>. Measured (a licence for another project wrote a PANIC line at start):

"rid":"XDB","atr":"sta","fnc":"xdbsta_pnc","valr":"0x004C","why":"log PANIC +1"

ALM.consta

The same for a <con>: consta_<why> (consta_lnk, consta_wdt …). See 12_Keeping_It_Running.

ALM.thrsta

The same for a <thr>. Measured with thr_alm_wdt="0,1,60" and a callback that slept 2.5 s:

"rid":"TH_SLOW","atr":"sta","fnc":"thrsta_wdt","valr":"0x0048","why":"worker 0 running one node for 1 s"

ALM.send

ALM.send(evt, stan, fnc, valr) → result code

Raises or clears an alarm from a script function in a chain: the level of stan goes into the element's sta when the chain ends (NEW set when it is not 0), with the WARN line and the record fnc names.

Argument Meaning
evt the chain's event; the alarm is on its element and attribute
stan a sta value; only its level bits are used: 0x0308 = ALARM, 0x0300 = normal
fnc the record's fnc
valr the record's valr

Returns 0x00000000 when the record was written, 0x80000002 when the document has no alm_adr (the level is set anyway), 0x80000008 with other than four arguments.

function check(evt)           // val_fnc="[main.check]"
{
    var r = ALM.send(evt, 0x0308, "custom", 42);
    evt.Log(4, "" + r + " " + evt.stan);    // 0x00000000 0x034B
    return 0;
}

After the call evt.stan already shows the new level, as it does after any alarm function in the chain.

IF: conditions

An IF.* function compares the value being written with an attribute. When it fails, every following function of the chain is skipped until IF.else or IF.end; the value itself is still stored. Measured with [IF.grt,ATR.rou] and val_if_grt="10": 5.555 stored as 5.555, 15.555 as 15.6.

Pattern Means
[IF.x,A,IF.end,B] A if x; B always
[IF.x,A,IF.else,B,IF.end,C] A if x, else B; C always
[IF.x,IF.y,A,IF.else,B,IF.end,IF.end,C] A if x and y, else B; C always

Several IF in a row are an AND, and IF.else is the else of the whole row. Close a row with one IF.end for each IF in it. One IF.end is not always enough, because an IF that is skipped is not counted: measured on [IF.grt,IF.les,main.a,IF.end,main.b] with limits 10 and 20, main.b ran for 5 and 15 and not for 25. With two IF.end it ran for all three. IF.else with no IF before it does nothing and both sides run.

The limit is <atr>_if_<name>: val_if_grt in a val_fnc, sta_if_and in a sta_fnc. No limit is 0. Every comparison is skipped while the element's run state is DISABLED.

Measured, each with [IF.x,main.hit]:

Function Limit Written → main.hit ran
IF.grt 10 5 no · 10 no · 15 yes
IF.gre 10 5 no · 10 yes · 15 yes
IF.les 10 5 yes · 10 no
IF.lse 10 10 yes · 15 no
IF.equ 10 10 yes, and 10 again yes
IF.equ ON "ON" yes · "on" no
IF.grt none 0 no · 1 yes
IF.set — 0→1 yes · 1→1 no · 1→2 no · 0→2 yes; text ""→"x" yes, "x"→"y" no
IF.rst — 1→0 yes · 0→0 no · 2→0 yes
IF.chg — 0→1 yes · 1→1 no
IF.and 2 4 yes · 2 yes · 0 no
IF.nand 2 4 no · 2 no · 0 yes
IF.in [2,4,6] 2 yes · 3 no

IF.equ

In: any <atr>_fnc. Reads: <atr>_if_equ. Goes on when the value equals it — on every such write, not only a change (add IF.chg for that).

IF.neq

Reads: <atr>_if_neq. Goes on when the value differs from it. val_if_neq="5" val_fnc="[IF.neq,main.f]": writes of 3, 5, 6 ran main.f for 3 and 6.

Before 4.4.2.703 the name was not registered: a chain with it wrote function 'IF.neq' not found and skipped it; use [IF.equ,IF.else,..] there.

IF.grt

Reads: <atr>_if_grt. Goes on when the value is above it.

IF.gre

Reads: <atr>_if_gre. Goes on when the value is at or above it.

IF.les

Reads: <atr>_if_les. Goes on when the value is below it.

IF.lse

Reads: <atr>_if_lse. Goes on when the value is at or below it.

IF.set

Reads: the previous value. Goes on only when the value goes from 0 to something else (for text: from empty to not empty).

IF.rst

Goes on only when the value goes from something else to 0 (text: to empty).

IF.chg

Goes on when the value differs from the stored one. The usual guard before history or a script: [ATR.rou,ALM.onlvl,IF.chg,HIS.val] (PRJEDU_records).

IF.and

Reads: <atr>_if_and. Goes on when both the value and the limit are not 0. It is a logical AND, not a bit test: 4 with a limit of 2 goes on. To act on one bit, address the bit itself (pro_adr="2.1", PRO.inp) or test it in a script.

IF.nand

Reads: <atr>_if_nand. The opposite: goes on when the value (or the limit) is 0.

IF.in

Reads: <atr>_if_in, a list of whole numbers in brackets: "[2,4,6]".

IF.else

Turns the current answer round: what was skipped runs, what ran is skipped. Inside a role section (IF.edge …) it turns the section round instead — do not mix the two.

IF.end

Ends one IF. When every IF of the row is ended, the chain runs again whatever the answer was. It does not end a role section.

IF.alone

Role marks say which kind of document runs the part of the chain after them. The kind is the role class in the document's sta (10_Two_Engines): plain, edge (<doc sta="0x4300">) or hub (<doc sta="0x8300">). A section lasts until the next mark; IF.end does not close it, IF.any does.

IF.alone: what follows runs in a plain document.

IF.edge

What follows runs in an edge document.

IF.hub

What follows runs in a hub document.

IF.any

What follows runs in every kind.

An unmarked chain does not run in a hub document, with one WARN line the first time: HUB -- unmarked chain skipped ('[ELM.sta]'); write IF.hub / IF.any to run it at the centre. Measured with the same elements in three documents:

Chain plain edge hub
[main.a] a a —
[ATR.rou] (1.23456) 1.2 1.2 1.23456
[IF.any,ATR.rou] 1.2 1.2 1.2
[IF.alone,main.a,IF.edge,main.b,IF.hub,main.c,IF.any,main.d] a d b d c d
[IF.edge,main.a,IF.else,main.b] b a b
[IF.edge,main.a,IF.end,main.b] — a b —

A chain that must run on both sides starts with IF.any.

FILTER: holding a change back

A filter stops the chain and does not store the value while it holds a change back; "written to the database" in the help means stored in the attribute. The counters it keeps are attributes of the element (<atr>_flt_setcnt …), and a write that is an update passes every filter.

FILTER.setcnt

In: val_fnc. Reads: <atr>_flt_setcnt_cfg (a count). Changes: <atr>_flt_setcnt.

A change from 0 to something else is stored only after cfg more writes of it. A 0 in between starts again (one INFO line: flt.setcnt : id('SC')/@val value changed before the filter counter ran out). Any other change passes.

<var id="SC" val="0" val_typ="0x1104" sta="0x0303" sta_typ="0x1142"
     val_fnc="[FILTER.setcnt,main.hit]" val_flt_setcnt_cfg="3"/>

Five writes of 1: the first three are held (counter 1, 2, 3, val stays 0), the fourth is stored and runs main.hit. A debounce for a contact read at every poll.

FILTER.rstcnt

Reads: <atr>_flt_rstcnt_cfg. Changes: <atr>_flt_rstcnt. The same for a change to 0. With cfg="2", 1 → 0 was stored at the third write of 0.

FILTER.rpttim

Reads: <atr>_flt_rpttim_cfg (seconds). Changes: <atr>_flt_rpttim (the time, s).

After a change, writes of the same value within cfg seconds stop the chain. A change always passes. With cfg="3": 5, 5, 5 → only the first ran the chain; 4 s later 5, 5 ran it, the third did not; 6 ran it.

FILTER.chgtim

Reads: <atr>_flt_chgtim_cfg (seconds). Changes: <atr>_flt_chgtim.

A change passes and opens a window; further changes within cfg seconds are dropped — not delayed, dropped. With cfg="3": 1 stored; 2 and 3 a moment later were lost (val stayed 1); 4 s later 4 and 5 were stored, 6 right after was lost. A rate limit, not a "stable for N seconds" filter.

CTRL: the on-off controller

A thermostat-style controller on one element. Its fields:

Field Meaning
rmt 1: AyMON decides the output. 0: the device is the controller; AyMON mirrors it and passes on what an operator writes
mod 1 direct (heating: output 1), 2 reverse (cooling: output 2), 0 both
run 0 off, 1 on (manual), 2 automatic
val the measurement, copied from val_ctl_lnk at every run
set the set point
out the output: 0, 1 (out_ctl1_lnk), 2 (out_ctl2_lnk). Must exist in the element
ooc_his the switching tolerance
val_ctl_lnk, set_ctl_lnk, run_ctl_lnk, out_ctl1_lnk, out_ctl2_lnk addresses of the device's points
run_ctl_off, run_ctl_man, run_ctl_aut the device's values for off, manual, automatic

CTRL.inpOOC

In: the evt_fnc of a timer on the controller element. Reads: the fields above. Changes: val, out (and in local mode set and run), and the output links.

Without rmt or mod it writes ctl.inpOOC : rmt not defined (NOTICE) and does nothing.

  • rmt="1": val is copied from val_ctl_lnk. run="0" sets out 0 and writes 0 to the output link; run="1" sets out 1 and writes 1. run="2" (automatic): with mod 0 or 1 out is 1 (written to out_ctl1_lnk) while val is at or below set (ooc_his = hysteresis); with mod="2" out is 2 (1 written to out_ctl2_lnk) while val is at or above set. Measured: set="21", 20.8 → out 1 and the heater on; reversed, set="24", 25 → out 2 and the cooler on. Before 4.4.2.703 automatic switched nothing (out stayed 0): decide in a script with an older engine.
  • rmt="0": set from set_ctl_lnk, run from run_ctl_lnk (0, 1 or 2 by matching run_ctl_off/_man/_aut, anything else 0), out from the output links (mod="0": 1, 2 or 3 for both).

CTRL.outOOC

In: set_fnc, run_fnc, out_fnc of the controller. Reads: rmt, the links. Changes: the device's points.

Passes an operator's write on to the device: out to the output links (1 to out_ctl1_lnk, 2 to out_ctl2_lnk, the other gets 0); with rmt="0" also set to set_ctl_lnk and run to run_ctl_lnk as run_ctl_off/_man/_aut. A value CTRL.inpOOC wrote is not passed back.

A complete local controller, measured: the device's DSET 19.5 and DRUN 0x05 appear as set=19.5 run=1; writing set 22.5 made DSET 22.5, writing run 2 made DRUN 0x0D.

<var id="TRL" xdb_fnc="[XDB.evt]" sta="0x0303" sta_typ="0x142" sta_fnc="[EVT.sta]"
     evt="" evt_typ="0x1201" evt_thr="TH" evt_cfg="0x0002" evt_per="1" evt_fnc="[CTRL.inpOOC]"
     rmt="0" mod="1" run="0" run_typ="0x1104" run_fnc="[CTRL.outOOC]"
     set="0" set_typ="0x1308" set_fnc="[CTRL.outOOC]" val="0" val_typ="0x0308"
     out="0" out_typ="0x1104" out_fnc="[CTRL.outOOC]"
     run_ctl_off="0x00" run_ctl_man="0x05" run_ctl_aut="0x0D"
     run_ctl_off_typ="0x0144" run_ctl_man_typ="0x0144" run_ctl_aut_typ="0x0144"
     val_ctl_lnk="id('TEMP')/@val" set_ctl_lnk="id('DSET')/@val"
     run_ctl_lnk="id('DRUN')/@val" out_ctl1_lnk="id('DOUT')/@val"/>

PRO: the protocol chain functions

These are the same for every protocol; what a protocol adds is in 09_Connection_and_Protocol_Types. Where each one goes:

Element Attribute Chain
<con>, <dev>, <bi>, <io> sta_fnc [PRO.sta] (the engine runs it when sta_fnc is absent)
<bi> evt_fnc [PRO.pol] — the timer asks the device
<bi> pro_fnc [PRO.inp] — the answer into the points
<io> pro_fnc [VAL.put] to read; [PRO.out,VAL.put] to read and write
<io> val_fnc [PRO.put], [PRO.cnvr,VAL.cnv] … to write from val

A whole polled point that can also be written, from the measured loopback (one engine, a Modbus slave on 127.0.0.1 answering a master in the same document, as PRJEDU_modbus does with two):

<dev id="D1" pro_adr="1" pro_con="CN_MB" con_host="127.0.0.1" con_port="1502"
     sta="0x0303" sta_typ="0x1142" sta_fnc="[PRO.sta]">
  <bi id="BLK" xdb_fnc="[XDB.evt]" sta="0x0302" sta_typ="0x1142" sta_fnc="[EVT.sta,PRO.sta]"
      evt="0" evt_typ="0x1204" evt_fnc="[PRO.pol]" evt_cfg="0x0002" evt_per="1"
      pro_typ="0xD412" pro="" pro_fnc="[PRO.inp]" pro_adr="0" pro_len="10" pro_fni="3" pro_fno="6">
    <io id="LEVEL" pro="0" pro_typ="0x1102" pro_adr="0" pro_fnc="[VAL.put]" sta="0x0302" sta_typ="0x1142"
        val="0" val_typ="0x1308" val_fnc="[VAL.cnv,ATR.rou,ALM.onlvl]" val_cnv_dlt="0.1" val_rou="0.1"
        val_alm_onlhi_alm="70"/>
    <io id="SP" pro="0" pro_typ="0x1102" pro_adr="6" pro_fnc="[PRO.out,VAL.put]"
        sta="0x0302" sta_typ="0x1142" val="0" val_typ="0x1104"/>
  </bi>
</dev>

Register 0 = 724 gave LEVEL pro=724 val=72.4 sta=0x034B. Writing SP.pro 150 left SP at 100 until the next poll brought 150 back into pro, and through VAL.put into val. The device counters on <dev> are pro_pol_snd, pro_pol_rcv, pro_pol_dur (ms), pro_out_snd, pro_out_rcv, pro_out_dur.

PRO.cre

In: xdb_fnc. Changes: sta_fnc.

Puts PRO.sta at the head of the element's sta_fnc: none → [PRO.sta]; [main.x] → [PRO.sta,main.x] (measured). The protocol named in a <con>'s xdb_fnc does the same for its <con>.

PRO.sta

In: sta_fnc of <con>, <dev>, <bi>, <io>. Reads: the command and run nibbles. Changes: sta of the element and of the ones below it.

Turns a command into a run state and carries it down the tree:

Written <con> <dev> / <bi> / <io>
START (0x03xx) from below START the connection starts WAITING, and the ones below WAITING; a point is RUNNING only when an answer lands
STOP (0x01xx) the connection stops RESTING (run nibble 1)
DISABLE (0x00xx) off run nibble 0 (a <dev> written 0x0000 left its blocks and points at 0x0300); a <dev> closes its own session (device left STARTED, closing CLISES(1))
INH on an <io> the alarm level cleared

In a plain document it also runs ALM.devsta for each <dev>. On a <con> it also takes an acknowledgement of the health bits (12_Keeping_It_Running).

PRO.open

In: pro_fnc of a <con>. Reads: the value written to the <con>'s pro. Changes: the connection.

pro = 0 closes the connection (PRO.open: connection cut); measured, the <con> then reads sta=0x0000, its devices 0x0340, its points 0x0301. Writing 1 afterwards does nothing: the connection is off. Writing its sta 0x0303 brought it back and the polls went on.

PRO.pol

In: evt_fnc of a <bi>. Reads: pro_con and pro_adr of the <dev>; pro_fni, pro_adr, pro_len of the <bi>; the timing fields below. Changes: the <bi>'s pro, its sta, the <dev>'s counters.

Builds one request from the block, sends it, and writes the answer into the block's pro, which runs its pro_fnc (PRO.inp). The timer lives on the <con>'s thread unless evt_thr says otherwise. No poll is made while the <dev> is commanded STOP or below.

If no answer comes, nothing is distributed: the points keep their last value, and only the last failed attempt takes the block and its points to WAITING. Measured with a peer that accepts the connection and never answers (pro_tmo="0.5" pro_try="2" pro_faildly="1.5" on the <dev>):

SBLK:PRO.modbus(2).pro.pol: @pro : Error(ERR_RECEIVE_TIMEOUT)
SBLK:PRO.modbus(2).pro.pol: @pro : retry 1/2 queued in 1500 ms (ERR_RECEIVE_TIMEOUT)
...
SBLK:PRO.modbus(2).pro.pol: @pro : retry budget exhausted, 3 attempts (requests in a row without an answer)
SBLK:PRO.modbus(2).pro.pol: no answer to 3 request(s) in a row -- the device is asked less often until it answers (next in 500 ms, then up to con_rct 5000 ms)
ALM.devsta_nbi: id('DSLOW')/@sta ! 'sta' -> sta = 0x034A

After that the polls (evt_per="2", con_rct="5") came 2.5, 2, 4, 6, 6 s apart; the first answer ends the pause.

Field On Unit Meaning
pro_tmo <con> or <dev> s how long to wait for the answer
pro_try <con> or <dev> count retries after a failed request: 2 = 3 attempts (log: pro_try = 2 retries (3 attempts))
pro_faildly <con> or <dev> s the gap before a retry; nothing waits on it
pro_refreshdly <con> or <dev> s after a write that succeeded, read the block back this much later
pro_senddly, pro_readdly <con> or <dev> s, at most 1 pauses inside one exchange (a shared RS-485 line)
con_rct <con> s the longest pause for a device that does not answer, and the redial wait

A retry is made only after a time-out, a checksum error or a wrong answer, never after a failed connection. Measured pro_refreshdly="0.3" with evt_per="10": a write came back into pro within the second, not ten seconds later.

PRO.inp

In: pro_fnc of a <bi>. Reads: the block's pro, each child's pro_typ, pro_adr, pro_len, pro_swp. Changes: the pro and sta of every child.

Cuts the block into its points. Leave it out and every poll succeeds and no <io> moves.

  • pro_typ of the <bi> is a buffer, and its element is the unit of everything else: 0xD412 16-bit, 0xD411 bytes. pro_len counts those elements.
  • pro_adr of an <io> is the element it starts at. "N.b" is bit b of element N; the bit may run past the element (0.19 is bit 3 of element 1).
  • pro_typ of the <io> says how much it takes: 0x1102 one 16-bit element, 0x1111 one bit, 0x1104 / 0x1304 two elements (U32 / F32).
  • pro_swp: 1 swaps the bytes of each 16-bit word, 2 the 16-bit words of each 32-bit, 4 the 32-bit halves of each 64-bit. It is for numbers only.
  • A point outside the block stays WAITING, without a line.

Measured on registers 724, 8, 1, 2, then 12.5 as a float in registers 4–5:

<io> pro_typ pro_adr pro_swp pro
A 0x1102 0 724
B 0x1111 1.3 1 (bit 3 of 8)
B2 0x1111 1.2 0
B19 0x1111 0.19 1
C 0x1104 2 131073 (0x00020001: the first register is the low word)
C2 0x1104 2 2 65538 (0x00010002: high word first, as most Modbus devices send)
C3 0x1102 2 1 256
F 0x1304 4 12.5
S1 0x1401, pro_len="4" 0 1 or none "BADC" from 0x4142 0x4344: text keeps each register's bytes swapped
OOR 0x1102 12 0, sta=0x0302

PRO.vrec

In: an <atr>_fnc of a <bi>. Distributes the block like PRO.inp, into the children's attribute of the same name, by <atr>_adr. It does not apply pro_swp (measured: the point that read 65538 under PRO.inp read 131073). On pro, use PRO.inp.

PRO.out

In: pro_fnc of an <io>. Reads: pro_fno (of the <io>, else of its <bi>), pro_ado (else pro_adr) of the <io> and the <bi>, pro_swp, the <dev>'s pro_adr. Changes: the device; pro_out_snd / pro_out_rcv.

Sends what was written to pro and ends the chain without storing it. The device's answer comes back into the same pro with the next read and runs the functions after PRO.out — so [PRO.out,VAL.put] is read and write in one point. A value that came from the device passes PRO.out to the next function.

Situation Measured
sent SP:PRO.modbus(1).pro.out: [150] -> @pro : OK; pro 100 until the next poll, then 150
a point nothing reads back pro stays at its old value for good: use PRO.outc
the protocol cannot write, no link one ERROR line NOT SENT, nothing stored
the device refused one ERROR line, not repeated
the <dev> is switched off stored in pro, not sent, no line; the next poll after the device comes back overwrites it

PRO.outc

As PRO.out, but after a successful send the chain goes on with the value written, and it is stored. For a point that is never read back: an output nothing polls, a publish-only topic (PRJHW_fan). Measured [PRO.outc,main.after]: pro 33 at once, main.after saw 33.

PRO.outf

Sends every value written to pro, also one that came from the device, and ends the chain. Measured in a polled block: every poll wrote the reading straight back to the device (pro_out_snd up by one a second) and pro was never stored. Use PRO.out.

PRO.put

In: val_fnc of an <io>. Reads: <atr>_put (else the value written). Changes: the <io>'s pro.

Writes the value (or a fixed val_put) into pro as an outgoing value, so its pro_fnc (PRO.out) sends it; the chain goes on and val is stored. A value that came from the device passes.

<io id="SV" pro="0" pro_typ="0x1102" pro_adr="7" pro_fnc="[PRO.out,VAL.put]"
    sta="0x0302" sta_typ="0x1142" val="0" val_typ="0x1104" val_fnc="[PRO.put]"/>

val = 77: val 77 at once, [77] -> @pro : OK, and the next poll's value in both.

It writes the stored value at every start of the device

A point with VAL.put in pro_fnc and PRO.put (or PRO.cnvr, PRO.set) in val_fnc writes its stored pro to the device whenever the device's session starts, and its val becomes that pro. Measured: the register was 66 on the device, the point held 0; switching the <dev> off and on wrote [0] -> @pro : OK and the register became 0. Keep the write path (PRO.out in pro_fnc) and write pro, or accept that a restart restores the last value.

PRO.set

In: val_fnc. Writes 1 into pro (as ATR.set) to be sent, and ends the chain: val is not stored; it follows the device. Measured: val = 5 sent [1] and left val 1.

PRO.rst

As PRO.set with 0. Measured: val = 9 on a point with pro 7 → pro 0, val kept 5.

PRO.cnv

In: val_fnc. Reads: <atr>_cnv_dlt, <atr>_cnv_ofs. Writes val × dlt + ofs into pro and ends the chain. Measured val_cnv_dlt="0.1": val = 50 → pro 5, val kept.

PRO.cnvr

The reverse: pro = (val − ofs) / dlt, then ends the chain. The pair for an engineering value that is written:

<io id="CV" pro="0" pro_typ="0x1102" pro_adr="8" pro_fnc="[PRO.out,VAL.put]"
    sta="0x0302" sta_typ="0x1142" val="0" val_typ="0x1308"
    val_fnc="[PRO.cnvr,VAL.cnv]" val_cnv_dlt="0.1"/>

val = 7.7 sent [77] -> @pro : OK and left val as it was; the device's value then came back through VAL.put and VAL.cnv (PRO.cnvr lets a reading pass).

PRO.map

In: val_fnc. Runs ATR.map on the value and ends the chain: the value is not stored and nothing is written to pro.

PRO.mapr

As PRO.map with ATR.mapr.

PRO.req

Does nothing useful: it ends the chain, so the value is not stored. On a <con> it also writes a PANIC line, CN_MB:PRO.inp: connection not found, which puts the document in EMERGENCY. Do not use it.

PRO.upd

Does nothing; the chain goes on.