PRJEDU_plc — a PLC program for a bottle filling line

Every file of this example — the XML, the scripts, the page — is in PRJEDU_plc on GitHub. Run it with run.bat (Windows) or ./run.sh (Linux) from that folder.

The laboratory of an automation course, in one engine: a filling machine whose signals arrive over a fieldbus, a PLC program that runs it, and an HMI to operate it from.

run.bat

Then open http://127.0.0.1:8093/ and press START.

On Linux the same example starts with ./run.sh (the engine in ../bin/linux-x64; see "On Linux" in the top README).

Document Role What it is
PLT/S00 the machine a conveyor, bottles, a filling nozzle, two photo-eyes, a level switch, a supply tank and the operator's buttons. Its signals are a remote I/O: four Modbus TCP holding registers on 127.0.0.1:1503
CTL/S00 the PLC polls the remote I/O every 100 ms, runs its program every 100 ms, writes the outputs back as one register. And the HMI page

The PLC never reads the machine's document. Everything it knows comes over Modbus, as it would from a real remote I/O. Point <dev id="RIO"> at a real one and the program does not change.

The machine

entry        filling position              exit
x = 0 ...... x = 100 (nozzle, PE_FILL) .... x = 150 (PE_EXIT) .... 170
============ conveyor, 10 cm/s ============
                    |
              [ supply tank ]
Register Bits
0, inputs 0 PE_FILL bottle under the nozzle · 1 LS_FULL bottle full (92 %) · 2 PE_EXIT · 3 ESTOP_OK · 4 START · 5 STOP_OK · 6 RESET · 7 TANK_LOW (under 15 %)
1 level of the bottle at the nozzle, 0.1 %
2 supply tank, 0.1 %
3, outputs (the PLC writes) 0 conveyor · 1 valve · 2 RUN lamp · 3 FAULT lamp · 15 life bit
  • The nozzle hits a bottle's mouth only within 3 cm of it. Anywhere else the product goes on the floor. PE_FILL sees exactly those 3 cm, no more: the PLC's valve interlock trusts it, so PE_FILL = 1 has to mean "the nozzle would fill this bottle" (see "What it measured" for what happened when the beam reached 1 cm further).
  • A bottle that leaves with 90 % or more is good, anything less a reject. Past 100 % it overflows.
  • The supply tank empties by 2 % per bottle.
  • STOP and EMERGENCY STOP are normally closed contacts, as on every real machine: the input is 1 while all is well, so a cut wire stops the machine instead of hiding the button.
  • The remote I/O has a fault state: if the PLC's life bit stops flipping for 1.5 s, every output goes off.

The program

main.scan in db\db_CTL.js, once every 100 ms, top to bottom, like a PLC scan: read the input image, run the program, write the output image. The program is a step sequence, the SFC / GRAFCET of the course:

Step Outputs Next when
0 IDLE all off START (rising edge) → 1
1 CONVEY conveyor bottle at PE_FILL → 2
2 POSITION — 0.3 s → 3
3 FILL valve LS_FULL → 4 · 10 s without it → FAULT · the bottle gone → FAULT
4 DRIP — 0.5 s → 5
5 RELEASE conveyor the bottle has left PE_FILL → 1, or 0 after STOP
8 FAULT FAULT lamp flashing RESET → 0
9 E-STOP FAULT lamp steady pulled out, then RESET → 0

Around the sequence, the things a PLC program is judged on:

  • Edges. START and RESET act on the moment they are pressed, not for as long as they are held. The program keeps last scan's inputs (M_START, M_RESET) and compares.
  • An interlock. The valve output is step 3 AND a bottle under the nozzle, whatever the sequence says. A bug in the sequence cannot open it over an empty conveyor. It is only as good as the sensor it trusts: in the first version of this example the photo-eye saw further than the nozzle reached, and the interlock let the valve pour beside a bottle.
  • STOP finishes the bottle under the nozzle, then stops. EMERGENCY STOP stops everything at once and needs a RESET after it is pulled out.
  • Each end watches the other. The PLC faults when the remote I/O has not answered for 1 s (T_WATCHDOG). The remote I/O switches its outputs off when the PLC's life bit stops flipping for 1.5 s. Without the second, a cut cable leaves the valve open. The first version of this example had only the PLC's watchdog, and a pulled cable overflowed a bottle and put 594 bottle-% on the floor before anyone noticed.
  • The engine takes the input word apart, not the program: each input is an <io> with a bit address (pro_adr="0.3" is register 0, bit 3), so the program reads I_ESTOP_OK, not register 0 AND 8.

What the HMI shows

  • The line: bottles with their fill level, the nozzle and its stream, the photo-eyes' beams, the tank, the lamps, and the remote I/O's fault state.
  • The machine's panel: START, STOP, RESET and a latching EMERGENCY STOP. On the bench, three things a real machine does to you: refill the tank, pull the fieldbus cable, change the conveyor speed.
  • The program: the step sequence with the active step lit, how long it has been there, whether a STOP is pending, and the fault.
  • I/O monitor: every input and output bit as the PLC sees it, and the two analog values.
  • Production: bottles filled (the PLC's count), good, reject, overflow, spilled (the machine's), and the cycle time.

The page opens two live connections: the PLC's (8093, the page's own server) and the machine's (8094). Each document publishes only its own changes, so the page listens to both. A browser may open a WebSocket to any port.

What it measured

Run What happened
START, 70 s (engine 4.3.4.467, the first version) CONVEY → POSITION → FILL → DRIP → RELEASE, about 9 s a bottle, bottles stopped at x = 98 (within the nozzle's 3 cm). 7 bottles filled, 6 out as good, no reject, no spill, no overflow, 8.7 s per bottle
the first version, START, 20 runs of 40 s (engine 4.3.4.494, Windows, the page's two live connections open) its photo-eye reached 4 cm, the nozzle 3. Of 95 stops, 3 were at x = 97, 66 at 98, 24 at 99, 2 at 100. At 97 the beam saw the bottle and the nozzle missed it: for the PLC a bottle was under the nozzle, so FILL opened the valve and the interlock let it, the product went on the floor (200 bottle-% in 10 s), and the line faulted with not full after 10 s - is the supply tank empty? although the tank was nearly full. Each time the PLC had reacted inside one machine step: poll, scan and output write in the same millisecond, the conveyor off before the bottle moved again. A fast reaction, not a slow one - nothing in the engine was out of order. On Linux (15 runs) the reaction never came inside one step: 75 stops, 66 at 98, 9 at 99
this version, the same 20 runs the photo-eye sees what the nozzle reaches. 100 stops: 3 at x = 98, 72 at 99, 20 at 100, 5 at 101 - every one under the nozzle. 80 bottles filled, 60 out as good, no reject, no spill, no overflow, no fault. Linux, 15 runs: 75 stops, 68 at 99, 7 at 100; 60 filled, no reject, no spill, no overflow, no fault, 8.4-8.8 s per bottle
STOP while filling the bottle under the nozzle was finished, then IDLE
EMERGENCY STOP while running everything off at once. START while it was pressed did nothing; pulled out + RESET + START ran again
supply tank at 3 % not full after 10 s - is the supply tank empty?. Refill + RESET + START finished the half-filled bottle and ran on
conveyor 40 cm/s the bottle overshot the photo-eye while the PLC reacted, and left the nozzle during FILL: the bottle left the nozzle while filling
pull the fieldbus cable while filling the PLC faulted after 1.1 s (no answer from the remote I/O for 1 s), the remote I/O switched all outputs off after 1.4 s. No overflow, nothing spilled. Plugged back in: the outputs followed the PLC again, RESET + START ran on
the page writes STEP or Q_WORD refused, and logged: CTL/S00:STEP.val: xdb_acl yazma reddetti (rol 0)

Try this

Do See
START, watch a few bottles the step sequence lighting up, and the I/O monitor following the machine
STOP while a bottle fills the RUN lamp flashes. The bottle is finished, then the line stops
EMERGENCY STOP, then START nothing. Pull it out: still nothing until RESET
conveyor 40 cm/s the PLC's reaction time is a distance. At 10 cm/s the beam sees the bottle at x = 98 and it stops at 98 to 101 (mostly 99), still under the nozzle. At 40 cm/s it moves 4 cm a machine step. What is the fastest speed that works?
pull the fieldbus cable while filling the PLC faults after 1 s, the machine's outputs go off after 1.5 s. Plug it back in, RESET, START
let the tank run dry the fill timeout. Refill, RESET, START
remove && pe_fill from the valve line in main.scan the machine runs exactly as before: this sequence never reaches FILL without a bottle. So why is the interlock there? (Think of the next person who edits the sequence.)
add a step a capper after the filler, or count bottles into cases of six and pause the line for the case change