PRJEDU_modbus — Modbus TCP, both ends, no hardware

Every file of this example — the XML, the scripts, the page — is in PRJEDU_modbus on GitHub. Run it with run.bat (Windows) or ./run.sh (Linux) from that folder.

One engine, one command, real Modbus frames on a loopback socket:

run.bat

On Linux the same example starts with ./run.sh (the engine in ../bin/linux-x64; see "On Linux" in the top README).

Then open http://127.0.0.1:8103/ — the monitoring side's page: the tank with its limits, the three bits of the status register as lamps, a trend, and every point as the wire sent it (pro) next to what it means (val) and its alarm state.

Two documents in the same process talk to each other:

Document Role What it is
PLC/S00 Modbus slave the plant. Listens on 127.0.0.1:1502, answers for unit 1, serves four holding registers that a timer keeps moving.
MON/S00 Modbus master the monitoring side. Polls those registers once a second and turns them into engineering values with limits and alarms.

Read db\db_PLC.xml first if you are putting AyMON where a device used to be, db\db_MON.xml first if you are reading a device that already exists. They are the same four levels seen from opposite ends.

What it teaches

  • the four levels every AyMON project has — <con>, <dev>, <bi>, <io>
  • that the block is the unit of communication and the point is the unit of meaning: 50 registers in one <bi> is one frame, 50 separate <bi> is 50 frames for the same data
  • what pro_len counts: elements of the block's own pro_typ. With pro_typ="0xD412" (a buffer of 16-bit units) pro_len="4" is four registers; with pro_typ="0xD411" (bytes) the same block is pro_len="8" and every <io> address below becomes a byte offset too
  • bit addressing: pro_adr="2.1" is register 2, bit 1 — the same unit as pro_len, so absolute bit 2×16+1 of the block. Three points in this example take three bits out of one status register with no script
  • that pro is the wire value and val is the meaning; nothing crosses between them until pro_fnc="[VAL.put]" says so
  • that scaling, rounding, clamping and alarms are configuration (VAL.cnv, ATR.rou, ATR.lmt, ALM.onlvl), not script
  • that plain Modbus is not a licensed feature — all of this runs unlicensed

The page

MON/S00 serves it itself, with two more connections: CN_WEB (HTTP, the files in www\) and CN_LIVE (MQTT inside a WebSocket on the same port, /mqtt). The page subscribes to MON/S00/+/val, /pro and /sta; the engine answers with the current value of every <io> at once and then sends each change. It only reads: xdb_acl="0xFFFFFFF1" on the document gives a page that did not log in (a Guest) read and nothing else. Both listen on 127.0.0.1 only (con_acl).

www\kit.js is the small toolkit the example pages share (connect, subscribe, what a sta word says, a trend chart); wwwpp.js is this page.

The register map

Unit 1, holding registers, served by PLC/S00:

Register Meaning Raw Engineering
0 tank level 0..1000 0..100 % (×0.1)
1 temperature 160..340 16..34 C (×0.1)
2 status word bit0 pump, bit1 valve, bit2 high temp three <io>
3 pump hours counts up h

Scaled integers, because a Modbus register is 16 bits and has no decimal point. Turning them back into engineering values is val_cnv_dlt in db\db_MON.xml — one attribute per point.

What the log looks like

PLC/S00:PLC: Modbus TCP slave on 127.0.0.1:1502, unit 1, holding registers 0..3
MON/S00:MON: polling unit 1 at 127.0.0.1:1502, holding registers 0..3, once a second
MON/S00:MON: pump STARTED
MON/S00:MON: level 79 %, temp 33.3 C, pump on, valve shut, hot 1, level sta 0x0303

Turn xdb_log up to 7 on the <xdb> root and on the <con>, <dev> and <bi> you care about, and the frames themselves are in the log — both sides of them:

MON/S00:TANK_BLK:PRO.modbus(1).M-Q[...]: 00 04 00 00 00 06 01 03 00 00 00 04
PLC/S00:CN_PLC:PRO.modbus(1).SLV-I[...]: 00 04 00 00 00 06 01 03 00 00 00 04
PLC/S00:modbus.MAS-Q[...]: 00 04 00 00 00 0B 01 03 08 02 63 01 34 00 01 00 05
MON/S00:TANK_BLK:PRO.modbus(1).M-R[...]: 00 04 00 00 00 0B 01 03 08 02 63 01 34 00 01 00 05

The file threshold and the element detail are two different settings: the root's xdb_log decides what the file accepts, each element's xdb_log decides how much that element produces. Raising only one of them changes nothing.

Pointing it at a real device

Change con_host and con_port on <dev id="TANK"> in db\db_MON.xml, and pro_adr to its unit id. Then set sta="0x0000" on <doc id="PLC/S00"> in db\AyXDB.xml so the simulated plant stays out of the way. Nothing else in db_MON.xml is about the simulator.

The other direction works as well: leave PLC/S00 running and point any Modbus master (a SCADA package, mbpoll, a PLC) at 127.0.0.1:1502 — change con_host to 0.0.0.0 first if it is on another machine.