1 — The element tree, and talking to a device

Run PRJEDU_modbus first. Everything below is in that example, twice: once as the device being polled and once as the device answering.


Three layers that are independent

Mixing these up is the most common mistake, so it is worth being explicit. The connection (how bytes travel), the protocol (what is said) and the element model (where the data is written) are three separate things:

<con xdb_fnc="[CON.tcp,PRO.modbus]">    connection + protocol
  <dev pro_con="CN_X" pro_adr="1">      device
    <bi pro_fni="3" pro_adr="0">        block — ONE request
      <io pro_adr="2.1">                point — ONE value

One <con> element sets up both the transport and the protocol:

<con id="CN_PLC" xdb_fnc="[CON.tcp,PRO.modbus]" con_mod="CLIENT"
     con_host="127.0.0.1" con_port="1502" .../>

CON.tcp makes the connection, PRO.modbus the protocol. The order matters — the connection is always written first. The same PRO.modbus works over a serial line by writing CON.ser instead; the <dev>, <bi> and <io> elements underneath do not change at all.

The four levels

Element What it is
<con> The connection and the protocol on it
<dev> One device. Bound to a connection by pro_con
<bi> One request. A register block, an SNMP group, an OPC UA read
<io> One value taken out of that request

One <bi> is one request. That is the rule to hold on to. Protocols with no notion of blocks keep the <bi> layer anyway, because it is the unit that gets sent.

<con> — the fields you will actually set

Field Meaning
con_mod CLIENT (we dial) or SERVER (we listen). Required — without it configuration fails
con_host / con_port Where to dial, or where to listen
con_ses How many sessions. With con_ses > 0 each <dev> gets its own conversation, so a slow device does not hold up the others
con_tmo Connect timeout, seconds, decimal allowed
con_rct Wait before reconnecting (s)
con_acl Who may connect: "10.40.1.*, 127.0.0.1". Wildcards * and ?. No field, no filtering

<con> — protocol fields common to every protocol

Field Meaning
pro_role MASTER (we ask) or SLAVE (we answer)
pro_tmo How long to wait for a reply (s)
pro_try Retries of a failed poll. 0 = one attempt
pro_faildly Gap between attempts (s)
pro_senddly / pro_readdly Pauses inside one exchange. This is how you pace a shared RS-485 line

On a slow device look at pro_tmo first; on a noisy line, pro_try.

<dev>, <bi>, <io>

Element Field Meaning
<dev> pro_con Which <con> to talk through — its id
pro_adr The device address: slave id in Modbus, endpoint URL in OPC UA
pro_pol_snd / pro_pol_rcv Requests sent / replies received. Written by the engine
<bi> pro_fni / pro_fno Read / write function (Modbus function code)
pro_adr / pro_len Start of the block, and how many elements it holds
pro The raw block. The reply lands here and is distributed from here
pro_typ What the block is made of — see below
<io> pro_adr Position inside the block
pro The raw value for this point
val The processed value — scaled, mapped, given a unit

Three things about addresses that catch everyone

pro_len counts elements, not bytes. The unit is whatever pro_typ says the block is made of. With pro_typ="0xD412" (a buffer of 16-bit words), pro_len="4" is four Modbus registers — eight bytes. With pro_typ="0xD411" (a byte buffer) the same 4 is four bytes.

pro_adr on an <io> can carry a bit. pro_adr="2.1" means element 2, bit 1 — and "element" is again the block's own unit, so in a 16-bit block that is bit 1 of the third register. PRJEDU_modbus puts three flags at 2.0, 2.1 and 2.2 inside one register.

pro is not val. The raw value from the wire lands in pro; the value your project uses is val. Nothing moves between them by itself — you say so. This is one point out of PRJEDU_modbus, complete:

<io id="TANK_LEVEL" pro="0" pro_typ="0x1102" pro_adr="0" pro_fnc="[VAL.put]"
    val="0" val_typ="0x1308" val_fnc="[VAL.cnv,ATR.rou,ATR.lmt,ALM.onlvl]"
    val_cnv_dlt="0.1" val_rou="0.1" val_min="0" val_max="100" val_unt="%"
    val_alm_onlhi_alm="95" val_alm_onlhi_wrn="85"
    val_alm_onllo_wrn="15" val_alm_onllo_alm="5"
    sta="0x0302" sta_typ="0x1142"/>

Read the two chains left to right and the whole point is in them:

  • pro_fnc="[VAL.put]" — take the raw value and hand it to val. This is the bridge. Leave it out and the raw value arrives correctly, val stays at zero, and nothing is logged; the point simply never moves. The same is true if you write pro_typ="0x0102" instead of 0x1102: the 0x1000 bit is what makes the chain run at all — see guide 2.
  • val_fnc="[VAL.cnv,ATR.rou,ATR.lmt,ALM.onlvl]" — scale it (val_cnv_dlt="0.1", so a raw 724 becomes 72.4), round it to val_rou, clamp it to val_min…val_max, then compare it with the four alarm limits and set the alarm bits in sta. No script anywhere.

Scaling, limits and alarms are configuration, not code. That is worth noticing before you reach for a script.

sta — one word, four nibbles

Every element has it, and you will read and write it more than any other field.

 0x F   F   F   F
    │   │   │   └── run state    what is actually happening (the engine writes this)
    │   │   └────── configuration write permission, alarm mode
    │   └────────── command       what you or the operator asked for
    └────────────── role          cluster / edge-hub (see the replication example)

Run state (bits 0–3), written by the engine — an observation, not an order:

0x0000 DISABLED
0x0001 RESTING — stopped
0x0002 WAITING — not communicating
0x0003 RUNNING — live
+0x0004 / +0x0008 / +0x000C WARNING / ALARM / EMERGENCY

Command (bits 8–11), written by you:

0x0000 DISABLE
0x0100 STOP
0x0200 PAUSE
0x0300 START

So sta="0x0303" is the normal thing to write: start it, and it is running. sta="0x0300" means start it, the engine will bring the run nibble up.

Two consequences worth knowing:

  • An alarm is not a separate object. It is bits inside the value's own sta. That is why an alarm raised at one engine arrives at a mirrored engine for free — see PRJEDU_rep.
  • To stop a running connection write 0x0000 or 0x0100. Writing 0x0300 to something already running is not a stop.

How a value actually travels

timer fires
  └─ <bi>  the protocol builds the request, sends it, reads the reply
      └─ <bi>@pro          the raw block
          └─ PRO.inp       distributed to each <io>@pro
              └─ pro_fnc   VAL.put — the bridge to val
                  └─ val_fnc   scaling, limits, alarm evaluation

For a poll to go out at all, four things must be true: the <dev> exists, its command nibble is not DISABLE, pro_con names a real <con>, and the session is connected. If any is missing the poll is skipped silently — that is not an error, it means "nothing to do".

If no data arrived, nothing is distributed. On a timeout the points are not written with zero; the last good value stays where it is. A plant that shows 0 because a cable came loose is worse than one that shows a stale reading you can see is stale.

Writing works the same way in reverse, with one rule: if a write times out, io.pro is not updated. The request went out; whether the device got it is unknown, so the next read decides rather than the engine guessing.

Reading the log

Every protocol logs traffic in the same shape:

CN_PLC:PRO.modbus(0).MAS-Q[1|12|RES_OKY]: 00 01 00 00 00 06 01 03 00 00 00 04
       └ protocol  └ session   └ device  └ bytes  └ result
                        └ Q sent · R received · I unsolicited

A Q with no R after it means the device is not answering. Unexpected I lines usually mean an addressing problem or two masters on one line.

Quick diagnosis

Symptom Look at
No request goes out at all dev/@sta and bi/@sta — DISABLE? Is pro_con spelled right? Is the timer running? (guide 2)
pro_pol_snd climbs, pro_pol_rcv does not Timeout. pro_tmo, the address, is the device on
Neither counter climbs The poll is never triggered — it is the timer or sta, not the protocol
Values arrive but val stays 0 pro_fnc="[VAL.put]" is missing
The block reads one element however many you asked for pro_len is being read in the wrong unit — check pro_typ
Writes go out, nothing changes pro_out_snd / pro_out_rcv. If sends climb and receives do not, the device is not answering
Values drop to 0 when the line dies Not expected — the last value should stay. Keep the log

Where next

This guide is the tree and one polled device. The connection itself — who dials, who asks, several services on one port, protocols that push instead of answering, and what to do when AyMON does not speak the protocol at all — is 05_Connections_and_Protocols. Who may reach any of it is 06_Access_and_Safety.